RegulatingControl

Specifies a set of equipment that works together to control a power system quantity such as voltage or flow.Remote bus voltage control is possible by specifying the controlled terminal located at some place remote from the controlling equipment.The specified terminal shall be associated with the connectivity node of the controlled point. The most specific subtype of RegulatingControl shall be used in case such equipment participate in the control, e.g. TapChangerControl for tap changers.For flow control, load sign convention is used, i.e. positive sign means flow out from a TopologicalNode (bus) into the conducting equipment.The attribute minAllowedTargetValue and maxAllowedTargetValue are required in the following cases:- For a power generating module operated in power factor control mode to specify maximum and minimum power factor values;- Whenever it is necessary to have an off center target voltage for the tap changer regulator. For instance, due to long cables to off shore wind farms and the need to have a simpler setup at the off shore transformer platform, the voltage is controlled from the land at the connection point for the off shore wind farm. Since there usually is a voltage rise along the cable, there is typical and overvoltage of up 3-4 kV compared to the on shore station. Thus in normal operation the tap changer on the on shore station is operated with a target set point, which is in the lower parts of the dead band.The attributes minAllowedTargetValue and maxAllowedTargetValue are not related to the attribute targetDeadband and thus they are not treated as an alternative of the targetDeadband. They are needed due to limitations in the local substation controller. The attribute targetDeadband is used to prevent the power flow from move the tap position in circles (hunting) that is to be used regardless of the attributes minAllowedTargetValue and maxAllowedTargetValue.

URI: cim:RegulatingControl
Type: Class

 classDiagram
    class RegulatingControl
    click RegulatingControl href "../RegulatingControl"
      PowerSystemResource <|-- RegulatingControl
        click PowerSystemResource href "../PowerSystemResource"


      RegulatingControl <|-- TapChangerControl
        click TapChangerControl href "../TapChangerControl"


      RegulatingControl : RegulatingControl.discrete

      RegulatingControl : RegulatingControl.enabled

      RegulatingControl : RegulatingControl.maxAllowedTargetValue

      RegulatingControl : RegulatingControl.minAllowedTargetValue

      RegulatingControl : IdentifiedObject.mRID

      RegulatingControl : RegulatingControl.targetDeadband

      RegulatingControl : RegulatingControl.targetValue

Inheritance

Attributes

Name URI Cardinality and Range Description Inheritance
discrete cim:RegulatingControl.discrete 1
boolean
The regulation is performed in a discrete mode direct
enabled cim:RegulatingControl.enabled 1
boolean
The flag tells if regulation is enabled direct
maxAllowedTargetValue cim:RegulatingControl.maxAllowedTargetValue 0..1
float
Maximum allowed target value (RegulatingControl direct
minAllowedTargetValue cim:RegulatingControl.minAllowedTargetValue 0..1
float
Minimum allowed target value (RegulatingControl direct
targetDeadband cim:RegulatingControl.targetDeadband 0..1
float
This is a deadband used with discrete control to avoid excessive update of co... direct
targetValue cim:RegulatingControl.targetValue 1
float
The target value specified for case input direct
mRID cim:IdentifiedObject.mRID 1
string
Master resource identifier issued by a model authority IdentifiedObject

Identifier and Mapping Information

Schema Source

  • from schema: http://iec.ch/TC57/ns/CIM/SteadyStateHypothesis/2.0#

Mappings

Mapping Type Mapped Value
self cim:RegulatingControl
native this:RegulatingControl